Integrating the library contents
6.1 Working with the library in SIMATIC STEP 7
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
Function Manual, 11.2017, A5E37764016-06-76
69
Interconnecting inputs and outputs of the block
Table 6- 5
1
•
For the block parameter “HW_Ident_Head” of FB291 enter the PROFINET diagnostic address of PSU8600
in hexa decimal format within your SIMATIC STEP 7 project. (1). (In the example: 8183.)
• Enter output address of the head module and for all the four outputs of the 5 parameters, shown in the
figure below (2).
• Interconnect the global data block (in the example “DB15 “PSU_Global”.”PSU”) at input parameter “Data”
of “FB291 SITOP_PSU8600_V2” (3). Syntax: “X”.Y
X = symbolic name of the block
Y = name of the “UDT_PSU8600_Data_V2”-type tag in the DB
Repeat step 2 for other function blocks (except FB300).
3 Interconnect the inputs and outputs of the function blocks with process tags or constants. A description of the
inputs and outputs, as well as the expected formats, types and units are given in the chapter
FB
SITOP_PSU8600_V2 (Page 15).
Connect the remaining parameters as required.
Save the changes in Main [OB33]. This completes the integration of the function blocks.