Integrating the library contents
6.1 Working with the library in SIMATIC STEP 7
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
72 Function Manual, 11.2017, A5E37764016-06-76
7 For the parameter “Diag_Address”, enter the PROFINET diagnostic address of the SITOP PSU8600 within
your SIMATIC STEP 7 project (8183).
Save the changes and close the window.
9 Follow the same procedure to call FB300 in OB86 and cyclic interrupt OB. In this example OB33 with the
same instance DB which is created in step 3.
This Diagnostic block holds only 100 alarms of assigned PSU8600. If there are more than
100 alarms, new alarms will be discarded.
To know the diagnostic and input address of FB300, refer section Start/diagnostic
(Page 46)address of the connected modules.