Working with the library
7.2 SIMATIC STEP 7
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
111
Note
If your
communication blocks are called cyclically (for example, in OB1), it results in a slow
behavior of the web server integrated in SITOP PSU8600 due to high communication load.
If there are not any high demands regarding accurate time behavior, you can also c
all the
communication blocks in a time
-controlled block (for example, OB35).