EasyManua.ls Logo

Siemens SITOP series - Status Displays and Signaling

Siemens SITOP series
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
13
Hardware and software requirements
4
Hardware requirements
Table 4- 1
Component
Article number
No. of compo-
nents required
Alternative
S7-1516
6ES7516-3AN00-0AB0
1
Other S7-1200 or S7-1500
Comfort Panel TP1200
Comfort
6AV2124-0MC01-0AX0 1 Other Comfort Panels
SITOP PSU8600 6EP3437-8MB00-2CY0 1 Alternatively, you can also use:
6EP3436-8MB00-2CY0
6EP3436-8SB00-2AY0
6EP3437-8MB00-2CY0
6EP3437-8SB00-2AY0
SITOP CNX8600 6EP4437-8XB00-0CY0 4 Optional
Alternatively, you can also use:
SITOP CNX8600 (4 x 5 A).
6EP4436-8XB00-0CY0
SITOP CNX8600 (8 x 2.5 A).
6EP4436-8XB00-0DY0
SITOP BUF8600
(100 ms/40 A)
6EP4297-8HB00-0XY0 2 Optional
Alternatively, you can also use
SITOP BUF8600
(300 ms/40 A).
(6EP4297-8HB10-0XY0) or
SITOP BUF8600 (4 s/40 A).
(6EP4293-8HB00-0XY0) or
SITOP BUF8600 (10 s/40 A).
(6EP4295-8HB00-0XY0).
SITOP UPS8600 6EP4197-8AB00-0XY0 2 Either two BUF8600 only or two
UPS8600 only or one BUF8600
and one UPS8600 can be add-
ed to PSU8600.
SITOP BAT8600
LiFePO4
6EP4143-8JB00-0XY0 5 Five BAT8600 LiFePO4 can be
added to UPS8600. Alternative-
ly you can use BAT8600 Pb
battery. All the batteries
plugged should be of the same
type.
Third-party battery 1 Only one battery can be con-
nected to UPS8600.

Other manuals for Siemens SITOP series