SIMATIC STEP 7 function blocks
5.6 FB SITOP_PSU8600_MainUnit
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
35
Structure of UDT_MainUnit_OUT data type
Int Maximum input current of the main module in milliampere.
Int Input voltage of the main module in millivolt.
(100 mV resolution)
Int Link voltage of the main module in millivolt.
Int Output current of the entire main module.
Byte Operating state of the main module. Refer to the section
Description of Device_Operating_state parameter below.
Power supply system is shut down.
1 = ErrorOff The power supply system was automatically shut down as a result of
operation under inadmissible operating conditions.
2 = ReadyForRestart After an automatic shutdown due to fault, the power supply system can
be reactivated by switching off and switching on the supply voltage.
3 = Boot The power supply system is powering up, all of the outputs are still
The power supply system is operating in the normal mode.
5 = Phasefail Phase failure of the supply voltage detected. The power supply system
can continue to operate in normal mode without any restrictions for a
6 = SystemOverload (IP) System overload detected within the permissible overload profile. The
power supply system is still operating in the normal mode.
7 = SystemOverload (OP) System overload detected outside the permissible overload profile.
Power supply system only operating with some restrictions.
8 = SystemOverload (PL) Very high, brief load peak detected. Power supply system is operating in
9 = Buffering Primary supply voltage has failed. Power supply system is operating in
System overload outside the permissible overload profile detected. The
power supply system is still operating in the buffer mode.
System overload outside the permissible overload profile detected. The
power supply system can only operate with restrictions.
Very high, transient peak load detected. Power supply system is operat-