SIMATIC STEP 7 function blocks
5.7 FB SITOP_PSU8600_Output
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
41
Structure of UDT_Output_OUT data type
Table 5- 22
Parameter
Data type
Description
Imax
Int Maximal current of the output in milliampere.
(Smallest resolution 10 mA)
Output_voltage
Int
Current output voltage in millivolt. (10 mV resolution)
Output_current
Int
Current output current in milliampere. (10 mA resolution)
Operating_state
Byte Current operating state
0 = Output manually switched off
1 = Output switched off (PROFINET/IE)
2 = Output switched off (prioritizing output 1)
3 = Output switched off (overload)
4 = Output ready for reset (reset)
5 = Output switched off (error)
6 = Output switched off (startup)
7 = Output switched on (normal operation)
8 = Output in overload mode
9 = Output current-limited (with derating)
10 = Output in overload mode (with derating)
11 = Output current-limited (with derating)
12 = Output is locked.
Parallel_mode
Byte Parallel mode active (0 = normal; 1 = output switched
parallel) → valid only for main module with 4 outputs.
Description of
Error
parameter
Table 5- 23
State
Meaning
Remedy/notes
0
No error
1 Output number not correct. Only use output numbers between 1 to 36. 1 PSU8600 +
4 CNX8600 8X = 36 outputs in total. (4 + 4x8 = 36)