SIMATIC STEP 7 function blocks
5.7 FB SITOP_PSU8600_Output
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
41
Structure of UDT_Output_OUT data type
Int Maximal current of the output in milliampere.
(Smallest resolution 10 mA)
Current output voltage in millivolt. (10 mV resolution)
Current output current in milliampere. (10 mA resolution)
Byte Current operating state
0 = Output manually switched off
1 = Output switched off (PROFINET/IE)
2 = Output switched off (prioritizing output 1)
3 = Output switched off (overload)
4 = Output ready for reset (reset)
5 = Output switched off (error)
6 = Output switched off (startup)
7 = Output switched on (normal operation)
8 = Output in overload mode
9 = Output current-limited (with derating)
10 = Output in overload mode (with derating)
11 = Output current-limited (with derating)
Byte Parallel mode active (0 = normal; 1 = output switched
parallel) → valid only for main module with 4 outputs.
1 Output number not correct. Only use output numbers between 1 to 36. 1 PSU8600 +
4 CNX8600 8X = 36 outputs in total. (4 + 4x8 = 36)