EasyManua.ls Logo

Siemens SITOP series - Page 89

Siemens SITOP series
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WinCC Faceplates
6.4 View: State, expansion modules
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
89
Figure 6-10
Elements
Table 6- 8
Screen
area
Parameter
Description
CNX8600
infor-
mation
Operating state
and <Text field>
The operating state displays various colors depending on the state
of CNX8600.
The <text field> displays the operating state as plain text.
Text
Number
Color
off
0
White
Shutdown after error
1
Red
Ready for restart
2
Red, flashing
Startup
3
White
Normal operation
4
Green
Buffer mode
5
Yellow
Out Output information
1-4, 5-8
If CNX8600_8X module is connected, you can select outputs 1 to 4
by clicking on "1-4" button and to select outputs 5 to 8, you can
click on "5-8" button.
U
out
[V]; (output n)
Displays the output voltage of output n in volts.
I
out
[A]; (output n)
Displays the load current of output n in ampere.
State; (output n)
Shows the state of output n. The following states are displayed:
Description
Color
Switched off manually.
Yellow
Ready to start. The power supply can be switched
back on. (For example, switched off remotely or
after overload with idle time.)
Red, flashing
The output was switched off due to an error.
Red