Parameterizing the SITOP UPS1600
6.1 Buffering an S7 IO controller, including the I/O when the power fails
SITOP UPS1600 under STEP 7 V12
28 Getting Started,
9. Under "Stop buffering voltage" enter the battery voltage value where buffering should be
stopped or accept the standard value of 18.50 Volt.
10. Deactivate the checkbox "Enable reset".
11. Save your project.
12. Load the parameters into the S7 IO controller.