5.2.2 Installing the measuring cell
Procedure
1. Clean residues o the thread of the enclosure.
2. If present, insert the ribbon cable insulation ① again.
3. Push the sensor electronics through the threaded hole.
4. Screw the measuring cell into the enclosure:
– The ribbon cable must be in S-shape between the two bushing pins, and must be tracked
with every rotation of the measuring cell.
– Ensure that the ribbon cables do not kink, pinch, strain or twist.
– Turn the measuring cell into the enclosure until it projects 2 to 3mm.
Replacing spare parts
5.2Replacing the measuring cell
SITRANS P320/P420
30 Service Manual, 11/2023, A5E44914141-AC