SITRANS FM100
A5E48762204-AA page 37
Parameter table Output 1/2 Temperature
Sub-
parameter
level 1
Sub-
parameter
level 2
Sub-
parameter
level 3
Description
Value range /
value list
Standard
value LPM
Standard
value GPM
disabled Output deactivated disabled
Alarm output
Function
List selection
Sets the basic
function
Limit function / window
function
Limit function
Output
Sets the electr.
Output
NPN/PNP/PP NPN
Switching
function
Sets the log.
switching function
NO/NC NO
Threshold
Value input
Sets the switching
threshold
MB start ≤ value ≤ Full
scale
1
lower
threshold
Sets the lower
threshold for
window function
Value threshold ≤
value ≤ MB start
1
Hysteresis
Defines the
switching
hysteresis
-9999.0 value
+9999.0
1
Filter factor
Factor for the
switching delay
x100 ms
0x value 60x
0
Direction
Defines the
effective direction
of the switching
delay
Up / Down / Both Down
4-20 mA
Value 4 mA
Measured value for
4 mA output
MB start ≤ value
value 20 mA
0
Value 20 mA
Measured value for
20 mA output
Value 4 mA ≤ value
Full scale
100
0-20 mA
Value 0 mA
Measured value for
0 mA output
MB start ≤ value
value 20 mA
0
Value 20 mA
Measured value for
20 mA output
Value 0 mA ≤ value
Full scale
100
2-10 V
Value 2 V
Measured value for
2 V output
MB start ≤ value ≤
value 10 V
0
Value 10 V
Measured value for
10 V output
Value 2 V ≤ value
Full scale
100
0-10 V
Wert 0 V
Measured value for
0 V output
MB start ≤ value ≤
value 10 V
0
Value 10 V
Measured value for
10 V output
Value 0 V ≤ value
Full scale
100
Frequency
output
max.
frequency
Value input
Frequency output
at "value at max.
Hz"
50-1000 Hz 500 Hz
Overflow
Overflow value in %
of the “value at
max. frequency"
1-100 [%] 1%
Value at 0 Hz Value at 0 Hz
MB start ≤ value
value for max. Hz
0
Value at max.
Hz
Value at "max.
frequency"
Value for 0 Hz <value
≤ Full scale
100
Control input
(only OUT1)
Control function for
MIN / MAX memory
reset
OFF, memory reset OFF
KofiCom
(only OUT1)
Factory calibration mode on output 1
IO-Link
(only OUT1)
This mode activates the IO-Link function on output 1