Diagnosing and troubleshooting
9.4 Fault codes and corrective actions
SITRANS F Ultrasonic flowmeters FST030 (HART)
98 Operating Instructions, 08/2017, A5E35971532-AC
159
Internal error
Internal error i
n transmitter. Turn off the power,
wait 5 seconds and turn on the power again. If
the error still exists, contact your local Sie-
mens representative.
160
Mass flow Value simulated. Disable 'Simulation' before
returning to normal operation
161
Volume flow Value simulated. Disable 'Simulation' before
returning to normal operation
162
Density Value simulated. Disable 'Simulation' before
returning to normal operation
163
Medium temperature Value simulated. Disable 'Simulation' before
returning to normal operation
166
Standard volume flow Value simulated. Disable 'Simulation' before
returning to normal operation
Only hydrocarbon
167
Totalizer 1 Value simulated. Disable 'Simulation' before
returning to normal operation
168
Totalizer 2 Value simulated. Disable 'Simulation' before
returning to normal operation
169
Totalizer 3 Value simulated. Disable 'Simulation' before
returning to normal operation