Diagnosing and troubleshooting
9.4 Fault codes and corrective actions
SITRANS F Ultrasonic flowmeters FST030 (HART)
108 Operating Instructions, 08/2017, A5E35971532-AC
ID/
Icons
Diagnostic
Action
Comment
268
Specific gravity Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Upper alarm limit"
Only hydrocarbon
269
Specific gravity Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter "Upper warning limit"
Only hydrocarbon
270
Specific gravity Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter "Lower warning limit"
Only hydrocarbon
271
Specific gravity Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Lower alarm limit"
Only hydrocarbon
272
Standard specific gravity Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Upper alarm limit"
Only hydrocarbon
273
Standard specific gravity Value above warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter "Upper warning limit"
Only hydrocarbon
274
Standard specific gravity Value below warning limit. Check process
conditions or align limit to normal operation.
Adjust parameter "Lower warning limit"
Only hydrocarbon
275
Standard specific gravity Value below alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Lower alarm limit"
Only hydrocarbon
276
LiquIdent Value above alarm limit. Check process condi-
tions or align limit to normal operation. Adjust
parameter "Upper alarm limit"
Only hydrocarbon