5.4 Potting
The sensor can be potted with silicon dielectric gel (non-toxic, transparent and self-healing
gel)
NOTICE
Electrical connections
Do not pot meter before electrical connections have been made.
Mix the two components of the potting kit well and pour into terminal box.
Let cure for approximately 24 hours at approximately 25°C (77°F). Curing time increases
by 100% per -10°C (-18°F).
Horizontal orientation Vertical orientation
Note
Gel can be penetrated with test instruments or be removed in case of cable replacement.
Connecting
5.4 Potting
SITRANS F M MAG 1100 sensor
Operating Instructions, 01/2018, A5E03433301-AC 39