Installing/Mounting
4.5 Potential equalization
SITRANS F M MAG 5100 W
22 Operating Instructions, 11/2010, A5E03063678-02
Figure 4-11 Cathodic protection
Isolate the sensor from cathodic protected pipes using insulated bolts.
Use bypass cable between the mating flanges
NOTICE
Remote mounted sensor versions
If the above is not acceptable, remote m
ounted sensors can alternatively be connected
as follows:
Connect coil current cable shield at sensor end via a 1.5 µF condensator
Make sure that electrode cable shield is not connected at both ends