MAG 8000 & MAG 8000 CT
22
SFIDK.PS.026.D9.02
4. Commissioning
FT/PDM Meter Display Parameter/data type Factory settings Data range
number version view Fix parameter or meter data that not are changeable
104 All O5 Reset customer totalizer 3 No Yes/no
105 All - Customer totalizer 3 reset date PS3 production date and time year-month-day T
hours:minutes:seconds
106 All - Flow rate 0 - 1.25 Qn (Q3)
107 All - Actual velocity 0 - 12500
108 All - Flowrate percent value 0-125% (Q4)
120 All - Actual flow meter status 0 0 to 255, binary presented with
information 1 for bit 0
1: Totalizer 1 or 2 changed or reset,
2: Tariff setting changed or reset,
3: Tariff register changed or reset,
4: Date - time changed,
5: Alarm have been active,
6: Fault log has been reset,
7: Hardware key has been activated,
8: Meter has been power Up
130 All - Menu active 63=all menus active 0 to 63, binary presented with information
1 for bit 0
1: Operator menu,
2: Meter info menu,
3: Service menu,
4: Log menu,
5: Statistic menu,
6: Revenue menu
131 All - Default operator menu index Totalizer 1 Totalizer 1, Totalizer 2, Actual Flow rate,
Fault codes, Customer Totalizer
200 All O4 Fault status 0 0 to 8191, binary presented with
information 1 for bit 0
1: Insulation error,
2: Coil current error,
3: Preamplifier overload,
4: Database checksum error,
5: Low power warning,
6: Flow overload warning,
7: Pulse A overload warning,
8: Pulse B overload warning,
9: Consumption interval warning,
10/L: Leakage warning,
11/E: Empty pipe warning,
12/C: Low impedance (high conductivity)
warning,
13/d: Flow limit warning
201 All - Alarm configuration list 254= Alarm 2 to 8 enabled 0 to 8191, See 200
202 All - Date of fault log reset PS3 production date and time year-month-day T
hours:minutes:seconds
203 All O4 Non optimal measure time 0
204 All - Reset the fault log and faults 2000-01-01 T 00:00:00
205 All - Call up acknowledge No Yes/no
206 All - Battery alarm level 10% 0-100%
208 All - Reset leakage fault No Yes / No
209 All - Reset consumption log fault No Yes / No
210 All - Insulation alarm output enable No Yes / No
211 All - Insulation fault hours 0
212 All - Insulation fault counter 0
213 All - Insulation fault appears 2000-01-01 T 00:00:00
214 All - Insulation fault disappears 2000-01-01 T 00:00:00
215 All - Coil current alarm output enable Yes Yes / No
216 All - Coil current fault hours 0
217 All - Coil current fault counter 0
218 All - Coil current fault appears 2000-01-01 T 00:00:00
219 All - Coil current fault disappears 2000-01-01 T 00:00:00
220 All - Amplifier alarm output enable Yes Yes / No
221 All - Amplifier fault hours 0
222 All - Amplifier fault counter 0