5.1.3 Menu overview
Flow tool parameter FT131 defines the default display information with selection between
Totalizer 1 (Index 1)
Totalizer 2 (Index 2)
Flow rate (Index 3, updated with selected measuring frequency)
Fault codes (Index 4)
Customer totalizer (Index 5 - resetable)
Default information is shown after power up and after no key operation for 10 minutes.
Flow tool parameter FT130 defines the accessible menus on the display with selection off:
Operator menu
Meter info menu
Service menu
Data logger menu
Statistic and leakage menu
Revenue menu
Disabling display of the menu data will not affect the operation of the functions.