Safety notes
2.4 Certificates
MAG 6000 I / MAG 6000 I Ex de transmitter
18 Operating Instructions, 04/2016, A5E02083319-AG
FM Class I, II, III, Div 1 approval
Compact version for MAG 3100/3100 P sensors DN 15 to 300 (½" to 12")
Hazardous area
Class I, Div. 1, Group A, B, C, D
i
O
i
i
i
i
I
O
I
I
I
I
I
O
I
I
I
I
Notes from control drawing
1. The non-intrinsically safe terminals (power rail) must not be connected to a device which
uses or generates more than 250/30 Vrms or DC.
2. The installation must meet the requirements of the National Electrical Code/Canadian
Electrical Code.
3. Conduit seal is required within 460 mm (18") from MAG 6000 I in hazardous areas
(Class I, Div. 1).
The control drawings are found on the CD-ROM shipped with the device and on the Siemens
homepage at http://www.siemens.com/flowdocumentation.
Control drawing (Page 99)