7.3 External input
MAG 6000 I / MAG 6000 I Ex de transmitter
48 Operating Instructions, 04/2016, A5E02083319-AG
Digital output
Digital output can be used to configure various settings:
Pulse (volume/pulse, pulse output, pulse width, pulse polarity, and time constant), see
Pulse menu diagram (Page 77).
Frequency (frequency output, max frequency, and time constant), see Frequency menu
diagram (Page 77).
Error settings (level and number), see Error level menu diagram (Page 77) and Error
number menu diagram (Page 78).
Limit settings (number of setpoints, setpoint settings, and hysteresis), see Direction/limit
menu diagram (Page 78).
Batch settings (quantity, time and counter settings, and time constant), see Batch menu
diagram (Page 79).
Note
When
relay is set to batch function, pulse/frequency is not available on digital output.
Relay outputs
Relay output can be used to configure various settings:
Error settings (level and number), see Error level menu diagram (Page 77) and Error
number menu diagram (Page 78).
Limit settings (number of setpoints, setpoint settings, and hysteresis), see Direction/limit
menu diagram (Page 78).
Batch settings (quantity, time and counter settings, and time constant), see Batch menu
diagram (Page 79).
See also
Current output (Page 76)
7.3
External input
By applying 11 … 30 V DC to terminals 77 and 78, it is possible to perform:
Batch control (start, stop, hold/continue)
Reset totalizer
Force/freeze output
Q
max
2 (night)
See external input menu diagram (Page 80).