Table 5-1 Menu items
Item Value Description
Device Communica‐
tion Address
1-247 Device address [Factory setting: 1]
Baud rate 1200, 2400, 4800, 9600, 19200,
38400, 57600, 76800, 115200
Communication speed
[Factory setting: 19200]
Parity/framing
Even, 1 stopbit
Odd, 1 stopbit
None, 2 stopbit
None, 1 stopbit
Communication parameters
[Factory setting: Even, 1 stopbit ]
Interframe Space 3.5-25 chars The minimum interframe space between two MODBUS RTU mes‐
sages in sequence (speci󹪝ed as 3.5 characters) is con󹪝gurable.
Range: 3.5 – 25 character times.
[Factory setting: 3.5 ]
Response timeout 0-25.5 sec. Max. response time.
Used in time critical applications, where low cycle times are re‐
quired. If the response is not ready within the Response timeout,
an exception code 6 (Busy acknowledge) is returned and the re‐
quest must be send again.
[Factory setting: 10.0 ]
Response Delay 0-255 msec. The minimum time from a slave receives a request until it returns
a response. This makes it possible to send data to slow masters
without overwhelming its receiver.
[Factory setting: 0 ]
TAG Flowmeter The TAG can be changed to any string up to 16 characters
[Factory setting: Flowmeter]
MODBUS SW version 1.00 Firmware version of the MODBUS module
MODBUS HW version 2 Hardware version of the MODBUS module
Comm. Status
Ok: xx
Bad: xx
Ok = Received messages without errors
Bad = Received messages with CRC errors
Reset after power down.
Frame status
PE: xx
FE: xx
PE = Number of parity errors
FE = Number of framing errors
Reset after power down.