Setup
3.4 Inputs and outputs
FST030
Function Manual, 04/2017, A5E35693328-AA
103
Bidirectional flow across zero with positive scaling
Lower range value
Low flow cut-off
Upper range value
Upper saturation limit
Lower saturation limit
Lower fault current
Span
Current output setting
Process value = Mass flow
Direction = Bidirectional
Loop current scale = 4-20 mA US
Upper range value = 400 kg/h
Lower range value = -100 kg/h
Fail-safe behaviour = Minimum current
Low flow cut-off = 25 kg/h