Setup
3.4 Inputs and outputs
FST030
Function Manual, 04/2017, A5E35693328-AA
111
Loop current scale
Description
Sets current output scaling according to desired measurement range.
Format:
<Nominal range> (<lower fault current>) <lower saturation limit> to <upper saturation limit>
(<upper fault current>) [<Description>]
Setting 4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR
4 to 20 mA (3.75) 4.0 to 20.8 (22.6) US
4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR
Setup → Inputs and outputs → Channel 1 - output with HART → Current mode
Upper range value
Description
Sets value at 100% of measuring span and corresponds to a loop current of 20 mA.
Setting and Default are sensor specific, depending on the setting in PV selection and
depending on the Units setting.
-10800000000.00 kg/h to +10800000000.00 kg/h
Setup → Inputs and outputs → Channel 1 - output with HART → Upper range value
Lower range value
Description
Sets value at 0% of measuring span and corresponds to a loop current of 0/4 mA.
Setting and Default are sensor specific, depending on the setting in PV selection and
depending on the Units setting.
-10800000000.00 kg/h to +10800000000.00 kg/h
Setup → Inputs and outputs → Channel 1 - output with HART → Lower range value