3.4 Inputs and outputs
FST030
Function Manual, 04/2017, A5E35693328-AA
113
3.4.3.11
Fail-safe value
Description
Output value in case of a fault and when fail safe mode configured to Fail-safe value.
Note
Important
Values
are specific to Channel 1.
Setting
3.5 mA to 25.0 mA
Default
3.5 mA
Related
Path
Setup → Inputs and outputs → Channel 1 - output with HART → Fail-safe value
3.4.3.12
Fail-safe minimum time
Description
Minimum time the output stays in fail-safe mode.
Setting
0 s to 100 s
Default
0 s
Related
Path
Setup → Inputs and outputs → Channel 1 - output with HART → Fail-safe minimum time
3.4.4
Channel 2 - output
3.4.4.1
Operation mode
Description
Operation mode - Sets the output functionality for channel operation.
Setting
Off; Current output; Frequency output; Pulse output; Status output
Default
Off
Related
Path
Setup → Inputs and outputs → Channel 2 - output → Operation mode