Setup
3.4 Inputs and outputs
FST030
138 Function Manual, 04/2017, A5E35693328-AA
3.4.5.6.7 Lower range value
Description
Sets value at 0% of measuring span and corresponds to Frequency value low.
Setting and Default are sensor specific, depending on the setting in Process value and
depending on the Units setting.
Setting
-108000000.00 kg/h to +10800000000.00 kg/h
Default
0.00 kg/h
Related
Path
Setup → Inputs and outputs → Channel 3 - input/output → Frequency output → Lower range
value
3.4.5.6.8 Damping value
Description
Time constant of damping filter for frequency output signal.
Setting
0.0 s to 100.0 s
Default
0.0 s
Related
Path
Setup → Inputs and outputs → Channel 3 - input/output → Frequency output → Damping
value
3.4.5.6.9 Fail-safe behaviour
Description
Frequency output reaction in case of a fault.
Setting
Minimum frequency; Maximum frequency; Last valid value; Current value; fail-safe value
Default
Last valid value
Related
Path
Setup → Inputs and outputs → Channel 3 -input/output → Frequency output → Fail-safe
behaviour
3.4.5.6.10 Fail-safe minimum time
Description
Minimum time the output stays in fail-safe mode.