Setup
3.4 Inputs and outputs
FST030
154 Function Manual, 04/2017, A5E35693328-AA
Change process value - selection enable the changing of the process value
Setting Off; Pressure; Medium temperature; Density; Kinematic viscosity; Sensor temperature;
Auxiliary temperature
Default
Off
Related
Path
Setup → Inputs and outputs → Channel 3 - input/output → Current input → Change process
value
3.4.5.10.3 Loop current scale
Description
Loop current scale - Selects current input scaling according to desired measurement range
and fail-safe mode.
Setting
4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR;
4 to 20 mA (3.75) 4.0 to 20.8 (22.6) US;
4 to 20 mA (0.00) 4.0 to 20.5 (22.0);
4 to 20 mA (2.00) 4.0 to 24.0 (25.0);
0 to 20 mA (0.00) 0.0 to 20.5 (22.0);
0 to 20 mA (0.00) 0.0 to 24.0 (25.0)
Default
4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR
Related
Path
Setup → Inputs and outputs → Channel 3 - input/output → Current input → Loop current
scale
3.4.5.10.4 Upper range value
Description
Upper pressure value that is mapped to the upper nominal range boundary selected by
current mode. Applicable if process value = Pressure.
Setting
-
Default
100000.0 Pa
Related
Path
Setup → Inputs and outputs → Channel 3 - input/output → Current input → Upper range
value