Maintenance and diagnostics
4.8 Simulation
FST030
288 Function Manual, 04/2017, A5E35693328-AA
Setting Off; Current output; Frequency output; Pulse output; Status output; Digital input; Current
input
Default
Off
Related
The setting of this parameter affects the setting options in parameter
Simulation value.
Path
Maintenance and diagnostics → Simulation → Simulation inputs and outputs → Channel 3 -
input/output → Operation mode
4.8.1.3.2 Simulation
Description
Enables or disables simulation of channel 3 input/output.
Setting
Disabled; Enabled
Default
Disabled
Related
Only if this parameter is set to Enabled, then the setting of parameter
Simulation value
will
be relevant.
Path
Maintenance and diagnostics → Simulate → Simulate inputs and outputs → Channel 3 -
input/output → Simulation
4.8.1.3.3 Simulation value
Description
Set the current value to be output on the channel when current output or current input
simulation is enabled.
Set the frequency value to be output on the channel when frequency output simulation is
enabled.
Set the pulse value to be output on the channel when pulse output simulation is enabled.
Set the signal level to be output on the channel when status output or digital input simulation
is enabled.
Setting
0 mA to 25 mA
Default
0 mA
Operation mode is set to Current output or Current input