Communication
5.2 HART (Channel 1)
FST030
Function Manual, 04/2017, A5E35693328-AA
311
HART device type (read only)
Description
The
identification can be entered. The ID uniquely identifies the device
when combined with the manufacturer identification and device type.
Communication → HART (Channel 1) → HART Device Type
HART device revision
Description
Displays device revision level defined in HART protocol.
Path Communication → HART (Channel 1) → HART revision
Response preambles
Description
The number of response preambles can be defined.
Setting 5 to 20
Communication → HART (Channel 1) → Response preambles
Dynamic variable mapping
Mapping of measured process variables
The assignment of the measured process values to HART device variables (PV - primary
variable; SV - secondary variable; TV - tertiary variable; and QV - quaternary variable) can
be modified and assigned as desired via local user interface or via HART interface using
SIMATIC PDM.
The process value assigned to current output 1 is automatically assigned to PV.
Freely selectable according to the setting options.