Note
##### signs in display
The display is unable to show the measured value. Change the measurement unit or the
resolution.
Changing a value:
1. Select the digit to be changed by pressing and keys.
2. Use key to increase the value and key and decrease the values.
3. Press key in the rightmost position to confirm the changes, or press key in the leftmost
position to escape the view without changing the value.
Note
Ensure that the new value is within the minimum/maximum range.
Changing the resolution:
1. Select decimal point by pressing and keys.
2. Move decimal point by pressing key (moves decimal point to the left) or key (moves
decimal point to the right).
In order to change the resolution of the process value shown in the operation view (for example
mass flow), change the resolution of one configuration parameter for this process value (for
example "Low Flow Cut-off" (menu item 2.2.1.5)). Any changes in resolution will change the
resolution of all configuration parameters for this process value as well.
The resolution can also be changed by setting the decimal places parameter for the selected
process value, for example the decimal places for process value mass flow is defined in
parameter menu item 2.2.1.4.
Operating
7.1 Local operation (HMI)
SITRANS FC330
120 Operating Instructions, 01/2019, A5E44030648-AB