ID Icons Message Cause/Action
215 CH3 simulated Disable the simulation to return to normal operation.
216 CH4 simulated Disable the simulation to return to normal operation.
217 Process values frozen Freezing of the process values is enabled either via a dig‐
ital input or the fieldbus. Disable the freezing of the process
values to return to normal operation.
218 Output channels forced Forcing is enabled either via a digital input or the fieldbus.
Disable forcing to return to normal operation.
219 CH2 loop current error Invalid loop current deviation detected. Check current out‐
put cable connection. Passive operation: check external
power supply.
220 CH3 loop current error Invalid loop current deviation detected. Check current out‐
put cable connection. Passive operation: check external
power supply.
221 CH4 loop current error Invalid loop current deviation detected. Check current out‐
put cable connection. Passive operation: check external
power supply.
222 Invalid Modbus register
mapping
At least one source register has been used multiple times.
Correct the register mapping.
223 Invalid Modbus coil config‐
uration
A coil has multiple assignments. Correct the coil configu‐
rations.
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
SITRANS FC330
188 Operating Instructions, 01/2019, A5E44030648-AB