EasyManua.ls Logo

Siemens SITRANS FC330 - Page 199

Siemens SITRANS FC330
280 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 11-12 Current output (Channels 2 to 4)
Description Channels 2 to 4
Signal range 0/4 to 20 mA
Resolution 0.4 μA
Load
Ex i: <470 Ω
Non-Ex: <770 Ω
Time constant (adjustable) 0.0 to 100 s
Fault current
Measurement range (mA)
Lower fault current (mA)
Upper fault current (mA)
4-20 NAMUR
3.8 - 20.5
3.5
22.6
4-20 US
4.0 - 20.8
3.75
22.6
4-20 NAMUR
4.0 - 20.5
2.0
22.0
4-20 US
4.0 - 24.0
2.0
25.0
0-20 NAMUR
0.0 - 20.5
0.0
22.0
0-20 US
0.0 - 24.0
0.0
25.0
Customized fail-safe mode
Last reliable value
Lower fault current
Upper fault current
Fail-safe value
Current value
Galvanic isolation All inputs and outputs are galvanically isolated PELV circuits with 60 V DC isolation from
each other and ground.
Maximum test voltage: 500 V AC
Cable Standard industrial signal cable with up to 3 twisted pairs with overall screen can be con‐
nected between the transmitter and the control system. Individual pair or overall screen is
optional depending on user requirements.
Voltage range Max. 24 V DC (active)
14 to 30 V DC (passive)
Table 11-13 Digital output
Description Channels 2 to 4
Pulse 41.6 µs to 5 s pulse duration
Resolution 1 μs
Frequency 0 to 12.5 kHz, 50 % duty cycle, 120 % overscale provision
Resolution 0.2 Hz
Load < 750 Ω
Time constant (adjustable) 0 to 100 s
Active 0 to 24 V DC, 87 mA, short-circuit-protected
Passive 3 to 30 V DC, 100 mA, short-circuit-protected
Functions
Pulse
Frequency
Alarm class / NAMUR status
Individual alarms
Technical data
11.5 Outputs
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB 199

Table of Contents

Related product manuals