Figure4-10 Cathodic protection
Isolate the sensor from cathodic protected pipes using insulated bolts.
Use bypass cable between the mating 󹪞anges
Note
Remote mounted sensor versions
If the above is not acceptable, remote mounted sensors can alternatively be connected as
follows:
Connect coil current cable shield at sensor end via a 1.5 µF condensator
Make sure that electrode cable shield is not connected at both ends
Installing/Mounting
4.8Potential equalization