Channel 3
Table A-107 Channel 3
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9103 Float / 4 Current output
value
Output current value if
configured to current
output.
- - Read
only
9128 Unsigned / 2 Error status Error status if config‐
ured to current output.
-
Bit 0: Overflow
Bit 1: Underflow
Bit 2: Fail mode
activated
Bit 3: Cable break
Bit 4: Output current
cannot be
established (read
back deviation > 0.1
mA)
Read
only
9140 Unsigned / 2 Status output Status value if config‐
ured to status output.
- 0 - 1 Read
only
9269 Float / 4 Pulse status
output
Amount done if config‐
ured to pulse output.
- - Read
only
9272 Unsigned / 2 Error status Error status if config‐
ured to pulse output.
-
Bit 0: The pulse
output has reached
the maximum pulse
output frequency
Bit 1: Fail mode is
activated
Read
only
9287 Unsigned / 4 Pulse counter Pulse output since
startup.
- - Read
only
9200 Float / 4 Frequency out‐
put value
Frequency value if con‐
figured to frequency
output.
- - Read
only
9203 Unsigned / 2 Error status Error status if config‐
ured to frequency out‐
put.
-
Bit 0: Overflow
Bit 1: Underflow
Bit 2: Fail mode
activated
Read
only
10503 Float / 4 Current input
value
Input current value if
configured to current in‐
put.
- - Read
only
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 309