Process value 2
Table A-110 Process value 2
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
11201 Unsigned / 2 Process value Process value config‐
ured to be monitored
Disabled
3000: Volume flow
3004: Mass flow
3006: Sound velocity
3008: Flow velocity
3040: Density
3042: Medium
temperature
3044: Pressure
3046: Viscosity
3048: RTD
temperature 1
3050: RTD
temperature 2
65535: Disabled
Read /
write
11262 Float / 4 Maximum value Drag indicator of maxi‐
mum value specified by
Process value (11201)
Min. floating
point value
[units depend‐
ing on proc‐
ess value]
- Read
only
11264 String / 32 Maximum value
timestamp
Shows timestamp of re‐
corded maximum value
specified by Process
value (11201)
- Read
only
11244 Float / 4 Minimum value Drag indicator of mini‐
mum value specified by
Process value (11201)
Max. floating
point value
[units depend‐
ing on proc‐
ess value]
- Read
only
11246 String / 32 Minimum value
timestamp
Shows timestamp of re‐
corded minimum value
specified by Process
value (11201)
- Read
only
11205 Unsigned / 2 Reset logging Command to reset the
drag pointers to the
process value's default
value.
- 1: Reset Write on‐
ly
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 313