EasyManua.ls Logo

Siemens SITRANS FST030 - Page 314

Siemens SITRANS FST030
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Process value 3
Table A-111 Process value 3
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
11202 Unsigned / 2 Process value Process value config‐
ured to be monitored
Disabled
3000: Volume flow
3004: Mass flow
3006: Sound velocity
3008: Flow velocity
3040: Density
3042: Medium
temperature
3044: Pressure
3046: Viscosity
3048: RTD
temperature 1
3050: RTD
temperature 2
65535: Disabled
Read /
write
11298 Float / 4 Maximum value Drag indicator of maxi‐
mum value specified by
Process value (11202)
Min. floating
point value
[units depend‐
ing on proc‐
ess value]
- Read
only
11300 String / 32 Maximum value
timestamp
Shows timestamp of re‐
corded maximum value
specified by Process
value (11202)
- Read
only
11280 Float / 4 Minimum value Drag indicator of mini‐
mum value specified by
Process value (11202)
Max. floating
point value
[units depend‐
ing on proc‐
ess value]
- Read
only
11282 String / 32 Minimum value
timestamp
Shows timestamp of re‐
corded minimum value
specified by Process
value (11202)
- Read
only
11206 Unsigned / 2 Reset logging Command to reset the
drag pointers to the
process value's default
value.
- 1: reset Write on‐
ly
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
314 Operating Instructions, 08/2018, A5E37367739-AD

Table of Contents

Related product manuals