Channel 2 output status
Table A-119 Channel 2 output status
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
8864 Unsigned / 2 Simulation Enables or disables
simulation of channel 2
output status.
0
0: Disabled
1: Enabled
Read /
write
8865 Unsigned / 2 Simulated value Signal level that is out‐
put on the channel
when simulation is ena‐
bled.
0 0, 1 Read /
write
Channel 2 output frequency
Table A-120 Channel 2 output frequency
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
8905 Unsigned / 2 Simulation Enables or disables
simulation of channel 2
output frequency.
0
0: Disabled
1: Enabled
Read /
write
8906 Float / 4 Simulated value Frequency value that is
output on the channel
when simulation is ena‐
bled.
1.0
[Hz]
0.0 - 12500.0 Read /
write
Channel 2 output pulse
Table A-121 Channel 2 output pulse
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
8973 Unsigned / 2 Simulation Enables or disables
simulation of channel 2
output pulses.
0
0: Disabled
1: Enabled
Read /
write
8978 Float / 4 Simulated value Pulse frequency value
that is output on the
channel when simula‐
tion is enabled.
0.0
[pulses/s]
0.0 - 12500.0 Read /
write
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
320 Operating Instructions, 08/2018, A5E37367739-AD