Channel 4 output pulse
Table A-131 Channel 4 output pulse
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9473 Unsigned / 2 Simulation Enables or disables
simulation of channel 4
output pulses.
0
0: Disabled
1: Enabled
Read /
write
9478 Float / 4 Simulated value Pulse frequency value
that is output on the
channel when simula‐
tion is enabled.
0.0
[pulses/s]
0.0 - 12500.0 Read /
write
Channel 4 input current
Table A-132 Channel 4 input current
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
10605 Unsigned / 2 Simulation Enables or disables
simulation of channel 4
output current.
0
0: Disabled
1: Enabled
Read /
write
10606 Float / 4 Simulated value Current value that is
output on the channel
when simulation is ena‐
bled.
0
[mA]
0 - 25 Read /
write
Channel 4 discrete input signal
Table A-133 Channel 4 discrete input signal
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
9336 Unsigned / 2 Simulation Enables or disables
simulation of channel 4
discrete input signal.
0
0: Disabled
1: Enabled
Read /
write
9337 Unsigned / 2 Simulated value Signal level that that
substitutes the input
signal on the channel
when simulation is ena‐
bled.
0 0, 1 Read /
write
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
324 Operating Instructions, 08/2018, A5E37367739-AD