Siemens SITRANS FST030 - Audit Trail; Operating Time; A.9.11 Audit Trail

Siemens SITRANS FST030
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
6247 Unsigned / 2 Alarm class Bit encoded selection
of alarm classes.
Applicable if simulation
mode = 2. Set bit
means alarm class sim‐
ulation activated:
Bit 0: Process value
alarm (PA)
Bit 1: Process value
warning (PW)
Bit 2: Maintenance
alarm (MA)
Bit 3: Maintenance
warning (MW)
Bit 4: Maintenance re‐
quired (MR)
Bit 5: Function check
(FC)
0 0 - 63 Read /
write
6249 Unsigned / 2 NAMUR status Bit encoded selection
of NAMUR status sig‐
nals. Applicable if simu‐
lation mode = 2. Set bit
means NAMUR status
signal simulation acti‐
vated:
Bit 0: Out of specifica‐
tion (PA, PW)
Bit 1: Failure (MW)
Bit 2: Maintenance re‐
quired (MR, MD)
Bit 3: Function check
(FC)
0 0 - 15 Read /
write
A.9.11 Audit trail
A.9.11.1 Operating time
Table A-136 Operating time
Modbus
register
Data type /
Size in bytes
Parameter Description Default value
[unit]
(unit register)
Value range /
Setting options
Access
level
6160 Unsigned / 4 Operating time
total
Operating time of the
transmitter.
-
[h]
- Read
only
6162 Unsigned / 4 Operating time Operating time of the
transmitter since last
startup.
-
[h]
- Read
only
Modbus communication
A.9 Modbus holding registers tables
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 329