Digital input - channels 3 to 4
Digital input - channels 3 to 4
The Digital input can be used to control device functions such as reset of totalizers, zero point
adjustment, force outputs, or freeze process values. You can set the delay time and the polarity.
Off
Reset totalizer 1
Reset totalizer 1
Reset totalizer 1
Reset all totalizers
Zero point adjustment
Force outputs
Freece process values
CH3 input function
Finished
Finished
Digital input
Delay time
Polarity
Next
Analog input - channels 3 to 4
Analog input - channels 3 to 4
The analog input can be configured to either Totalizer reset, Remote zero adjust or freeze
process values, force outputs.
Loop current scale
Process value
Upper range value
Lower range value
Fail-safe behavior
Next
Current input
Finished
CH3 current input mode
CH3 process value
Pressure
Medium temperature
Density
Kinematic viscosity
4 to 20 mA (3.50) 3.8 to 20.5 (22.6) NAMUR
4 to 20 mA (3.75) 4.0 to 20.8 (22.6) US
4 to 20 mA (0.00) 4.0 to 20.5 (22.0)
4 to 20 mA (2.00) 4.0 to 24.0 (22.0)
0 to 20 mA (0.00) 0.0 to 20.5 (22.0)
0 to 20 mA (0.00) 0.0 to 24.0 (22.0)
CH3 fail-safe value
Last valid value
Fail-safe value
6.6.1.5 Communication wizard
This wizard will guide you through the configuration of the communication interface.
Commissioning
6.6 Commissioning via local display
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD 67