INSTALLATION 3
21
SITRANS FX300
www.siemens.com/flow06/2009 - SFIDK.PS.050.F2.02 A5E02100423
3.4.2 Measurement of vapours and gases
Recommended installations
Recommended installationsRecommended installations
Recommended installations
Prohibited installation
1 Lower pipe bends
2 Condensate
DANGER!
Prohibited: Installing the device in a lower pipe bend 1, because there is a risk of condensate
forming 2.
Condensate can lead to cavitation and inaccurate measurement. Under certain circumstances
the device can be destroyed and the measured product can leak.
CAUTION!
It is absolutely necessary to maintain the required inlet and outlet runs.
1 Inlet and outlet falling
2 Rising inlet - falling outlet
MA_Siemens_Sitrans_FX300_R02_en_PRT.book Page 21 Monday, June 22, 2009 8:17 AM