4 ELECTRICAL CONNECTIONS
48
SITRANS FX330
www.siemens.com/flow 08/2022 - A5E36751269-AG EN
Value range applies only when connected to a switching amplifier with the following reference
values:
Open-circuit voltage U
0
= 8.2 VDC
Internal resistance R
i
= 1 kΩ
To ensure the value ranges,
a load R
L
between 250 Ω and 1 kΩ is recommended for the passive
transistor output with a nominal voltage of 24 VDC. If other loads are used,
caution is advised as
the range of values of the signal voltages then no longer corresponds to the range of values for
the inputs of process control systems and controls (DIN IEC
946).
For selection of measurement variable and adjustable data of the limit switch refer to chapter
"Me
nu description C - Setup", menu "C2.2.5 Limit Switch" and appropriate submenus.
N/C contact N/O contact
Switching value reached < 1 mA > 3 mA
Switching value not reached > 3
mA
< 1
mA
Table 4-2: Value range for NAMUR
C2.2.6 Invert Signal On
C2.2.6 Invert Signal Off
U
L
I
L
U
H
I
H
via load R
L
0...2 V 0...2 mA 16...30 V 20...100 mA
Table 4-3: Value range for transistor output
CAUTION!
The upper limit of the signal current must not be exceeded as this may damage the transistor
output.