OPERATION 6
75
SITRANS FX330
www.siemens.com/flow08/2022 - A5E36751269-AG EN
A11.1 Application Assistant - Liquids
Function Setting / Description
.1
.2 Units
.2.1 Volume Flow
Select unit (default: according to order specification or m
3
/h).
.2.2 Mass Flow Select unit (default: according to order specification or kg/h).
.2.3 Volume
Select unit (default: according to order specification or m
3
).
.2.4 Mass Select unit (default: according to order specification or kg).
.2.5 Temperature Select unit (default: according to order specification or °C).
.2.6 Pressure Select unit (default: according to order specification or bar).
.2.7 Density
Select unit (default: according to order specification or kg/m
3
).
.3 Process Process configuration.
.3.1 Fluid Select "Liquid".
.3.2 Medium Select "Water" or "Custom".
.3.3 Time Constant 0...100 s
.3.4 Low Flow Cutoff Enter low flow cutoff point in current volume flow unit.
.4 Operating Values Current process conditions in case they are not measured nor calculated.
.4.1 Oper. Temperature Input in selected unit.
.4.2 Oper. Pressure Input in selected unit.
.4.3 Oper. Density Input in selected unit.
.5 Current Output Current output configuration.
.5.1 Current Out. Meas. Select measurement variable for current output.
.5.2 0% Range The set value represents 4 mA at the current output. Usually 0% flow = 4 mA, but it is
also possible to define a higher flow value for 4 mA.
.5.3 100% Range The set value represents 20 mA at the current output. Usually 100% flow = 20 mA, but it
is also possible to define a lower flow value for 20 mA.
.5.4 Error Function Low / Off / High / Hold
.5.5 Low Error Current 3.5...3.6 mA, available if "Error Function = Low"
.5.6 High Error Current 21...21.5 mA, available if "Error Function = High"
.6 Binary Output Optionally configure the binary output.
.6.1 Function Select the binary output function:
Limit Switch / Status / Frequency / Pulse / Off
.6.2 Invert Signal On, Off
.7 Pulse Output This menu is available if "Binary Output Function = Pulse".
.8 Frequency Output This menu is available if "Binary Output Function = Frequency".
.9 Status Output This menu is available if "Binary Output Function = Status".
.10 Limit Switch This menu is available if "Binary Output Function = Limit Switch".
.11 Flow Totalizer Optionally configure the flow totalizer.
.12 Energy Totalizer This menu is available if a non-standard meter type has been configured (refer to "C6.3
Extras").
.13 1. Meas. Page One Value / Two Values / Three Values / One Value & Bargraph / Two values &
Bargraph
.14 2. Meas. Page One Value / Two Values / Three Values / One Value & Bargraph / Two values &
Bargraph
Table 6-22: A11.1 Application Assistant - Liquids