6 OPERATION
76
SITRANS FX330
www.siemens.com/flow 08/2022 - A5E36751269-AG EN
A11.2 Application Assistant - Saturated Steam
A11.3 Application Assistant - Superheated Steam
Function Setting / Description
.1
.2 Units Same options as in A11.1.2.
.3 Process
.3.1 Fluid Select "Steam".
.3.2 Medium Select "Saturated Steam".
.3.3 Time Constant 0...100 s
.3.4 Low Flow Cutoff Enter low flow cutoff point in current volume flow unit.
.4 Current Input
.4.1 Function Select "On" if applicable.
.4.2 Current Input Meas. Select "Temperature External" if "Function = On".
.5.1 Temp. Source1 Internal / External / External HART / Not Available
.5.2 Temp. Source2 Internal / External / External HART / Not Available
Temperature source 1 and 2 must be different.
.6 Operating Values Same options as in A11.1.4.
.7 Current Output Same options as in A11.1.5.
.8 Binary Output Same options as in A11.1.6.
.9 Pulse Output Same options as in A11.1.7.
.10 Frequency Output Same options as in A11.1.8.
.11 Status Output Same options as in A11.1.9.
.12 Limit Switch Same options as in A11.1.10.
.13 Flow Totalizer Same options as in A11.1.11.
.14 Energy Totalizer Same options as in A11.1.12.
.15 1. Meas. Page Same options as in A11.1.13.
.16 2. Meas. Page Same options as in A11.1.14.
Table 6-23: A11.2 Application Assistant - Saturated Steam
Function Setting / Description
This application assistant is available if meter type is set to "Heat & Dens. by Pres." or "Heat & Dens. & FAD" (refer to
"C6.3 Extras").
.1
.2 Units Same options as in A11.1.2.
.3 Process
.3.1 Fluid Select "Steam".
.3.2 Medium Select "Superheated Steam".
.3.3 Time Constant 0...100 s
.3.4 Low Flow Cutoff Enter low flow cutoff point in current volume flow unit.
.4 Current Input
.4.1 Function Select "On", if applicable.
.4.2 Current Input Meas. Select "Temperature External" or "Pressure External".
.5.1 Temp. Source1 Internal / External / External HART / Not Available