OPERATION 6
85
SITRANS FX330
www.siemens.com/flow08/2022 - A5E36751269-AG EN
C3.1.2.3 Long Tag Enter long measuring point identifier (1...32 digits).
Entry will be displayed in the header bar on the LC display (depending on letter size,
mi
n. 11 digits can be displayed).
C3.1.2.4 Manufacturer ID
HART
®
Manufacturer ID = 00042 (0x2A) [SIEMENS] (read-only)
C3.1.2.5 Device Type Device Type = 00058 (0x3A) (read-only)
C3.1.2.6 Device ID Individual device ID (read-only)
C3.1.2.7 Universal Revision
HART
®
revision (read-only)
C3.1.2.8 Device Revision (read-only)
C3.1.2.9 Software Revision (read-only)
C3.1.2.10 Hardware Revision (read-only)
C3.1.3 Device Information
Informative text can be added to describe the device in the HART
®
communication loop.
C3.1.3.1 Descriptor Commenting text to label instrument can be added; 1…16 digits.
C3.1.3.2 Message Here additional information can be added.
C3.1.3.3 Date Customer-defined date can be set here.
C3.1.3.4 Cfg. Change Counter Counter for changes in settings (read-only).
C3.1.4 HART Variables
Definition of HART
®
variables.
C3.1.4.1 Current Out. Meas.
Primary HART
®
variable; identical with current output measurement variable.
C3.1.4.2 Frequency Out.
Meas.
Secondary HART
®
variable; identical with frequency output measurement variable. If
binary output is not activated or not configured as frequency output, the secondary
HART
®
variable is selectable. The variable selection is depending on the device
configuration.
C3.1.4.3 Current Input Meas.
Tertiary HART
®
variable; identical with current input measurement variable. If the
current input is not activated, the secondary HART
®
variable is selectable. The variable
selection is depending on the device configuration.
C3.1.4.4 Quaternary HART Select (Availibility depending on fluid and medium configuration): Volume Flow / Norm.
Volume Flow / Mass Flow / Gross Power / Net Power / FAD / Volume / Norm. Volume /
Gross Energy / Net Energy / Density / Temperature1 / Temperature2 / Pressure /
Vortex Frequency / Velocity / Specific Enthalpy / Specific Heat Capacity / Reynolds
Number
C3.1.5 Catch DV Temp. Catch device variable allows for capturing process data from another field device in a
multidrop network.
C3.1.5.1 Capture Mode ACK - listen to responses by a specific slave device
BACK - listen to bursts by a specific slave device
OFF - disable capture mode
C3.1.5.2 Exp. Device Type Define expanded device type for source slave.
Enter: 000…65535
C3.1.5.3 Slave Device ID Enter source slave address
C3.1.5.4 Capture Command Select source command number: 1 / 2 / 3 / 9 / 33
C3.1.5.5 Slot Number Describes slot to process in response message. Select 1…8 (depending on source
command number).
C3.1.5.6 Shed Time Shed time for mapping.
Define: 0…max.
C3.1.6 Catch DV Pressure Same options as C3.1.5.
Table 6-31: Menu description C3
Function Setting / Description
C3 Communication