Page 30 SITRANS LR250 (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JF02
mmmmm
Quick Start: local
Quick Start Wizard via the handheld programmer
1. Quick Start
a. Point the programmer at the display (from a maximum distance of 300 mm [1 ft]),
then press RIGHT Arrow to activate PROGRAM mode and open menu level 1.
b. Press RIGHT Arrow twice to navigate to menu item 1.1 and open parameter
view.
c. Press RIGHT Arrow to open Edit mode or Down ARROW to accept default
values and move directly to the next item.
d. To change a setting, scroll to the desired item or key in a new value.
e. After modifying a value, press RIGHT Arrow to accept it and press Down
ARROW to move to the next item.
f. Quick Start settings take effect only after you select Yes to Apply changes in step 1.7.
1.1. Material
Selects the appropriate echo processing algorithms for the material (see Position
(2.2.3.1.3.) on page 113 for more detail).
1.2. Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater).
Notes:
• The Quick Start wizard settings are inter-related and changes apply only after you
select YES in Apply? (Apply changes) (1.7.)
• Do not use the Quick Start wizard to modify individual parameters: see instead
Parameter Reference
on page 51. (Perform customization only after the Quick Start
has been completed.)
Options
LIQUID
LIQUID LOW DK
1)
(low dielectric liquid – CLEF
algorithm enabled
)
1)
dK < 3.0
Options
1)
1)
See LOE Timer (2.4.1.) on page 73 for a table showing the effect of the Response
Rate settings.
SLOW 0.1 m/min (0.32 ft/min)
MED 1.0 m/min (3.28 ft/min)
FAST 10.0 m/min (32.8 ft/min)