EasyManua.ls Logo

Siemens Sitrans LR250 - Intrinsically Safe Wiring

Siemens Sitrans LR250
169 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 42 SITRANS LR250 (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JF02
mmmmm
SIMATIC PDM
5) In Step 5 – Summary, check parameter values. Click on BACK to return and revise
values, or TRANSFER to download settings to the device.
The message Quick Setup was successful will appear. Click on OK, then click on OK again to
synchronize with the device.
Configuring a stillpipe application
Launch the Quick Start wizard and follow steps 1 to 2.
In step 2, select Application Type – Level in a vessel with stillpipe; Material – Liquid
Low dK; and set the stillpipe diameter as desired. The wizard updates the
propagation factor according to the pipe diameter, and enables the CLEF algorithm
for low dK liquids (see
Position (2.2.4.1.2.)
on page 104 for more detail.
Continue through steps 3 to 5 then click on Transfer to download settings to the
device.

Table of Contents

Other manuals for Siemens Sitrans LR250

Related product manuals