Page 88 SITRANS LR250 (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JF02
mmmmm
Parameters
3.7.3. Event Diagnosis
Allows you to assign one of the diagnostic options listed below to any of the
events listed in Event Index (3.7.1.). This allows you to tailor a device response
appropriate for your particular process.(Event Diagnosis affects Condensed
Acyclic Diagnostics and Cyclic Extended Diagnostics
1)
).
To assign a diagnosis to a particular event via the handheld programmer:
a) Go to Condensed Status Mode (3.6.1.) and select Yes to enable Condensed
Mode.
b) Go to Event Index (3.7.1.) and enter the event index number corresponding
to a particular event.
c) Go to Event Diagnosis (3.7.3.) and choose a Diagnosis option from the table
above.
To assign a status to a particular event via SIMATIC PDM:
a) Go to Level Meter > Diagnostics > Condensed Status Setup, and select
Yes to enable Condensed Status Mode.
b) Go to Level Meter > Diagnostics > Condensed Status.
c) Select the Diagnosis line for the selected Event, then choose a Diagnosis
option from the associated pull-down menu.
Event Diagnosis Options
Status OK
Maintenance Required
Maintenance Demanded
* Maintenance alarm
Invalid process conditions
Function check or simulation
1)
See
Condensed Mode Diagnosis
on page 142 for more detail.