Commissioning
6.2 Programming SITRANS LR250
SITRANS LR250 with FOUNDATION FIELDBUS
Compact Operating Instructions, 09/2021, A5E48453221-AB
45
6.2.4 Programming via the handheld programmer
While the device is in PROGRAM mode the output remains active and continues to respond
to changes in the device.
The device automatically returns to Measurement mode after a period of inactivity in
PROGRAM mode (between 15 seconds and 2 minutes, depending on the menu level).
Parameter menus
Note
For the complete list of parameters with instructions, see the full operating instructions.
Parameters are identified by name and organized into function groups.
2.1. IDENTIFICATION
2.2. DEVICE
1. Enter PROGRAM mode
• Point the programmer at the display from a maximum distance of 300 mm (1 ft).
• RIGHT arrow
activates PROGRAM mode and opens menu level 1.
• Mode
opens the menu level last displayed in PROGRAM mode within the last 10
minutes, or menu level 1 if power has been cycled since then.
Maximum distance: 300 mm ( 1 ft)