Setting 0 to 99999
Default 1.0 m/min
Note
R
ate parameters
The rate parameters "Fill rate limit", "Empty rate limit", and "Damping value" work in conjunction,
and are a󹪜ected by parameter "Response rate" (set in the "Quick commissioning" wizard). The
rate parameters automatically adjust when parameter "Response rate" is altered, but any
changes made to the rate parameters following the completion of the wizard supersede the
response rate setting.
9.2.2.4 Empty rate limit (2.2.4)
Se
ts the maximum empty rate the device can track.
Setting 0 to 99999
Default 1.0 m/min
Note
R
ate parameters
The rate parameters "Fill rate limit", "Empty rate limit", and "Damping value" work in conjunction,
and are a󹪜ected by parameter "Response rate" (set in the "Quick commissioning" wizard). The
rate parameters automatically adjust when parameter "Response rate" is altered, but any
changes made to the rate parameters following the completion of the wizard will supersede the
response rate setting.
9.2.3 Calibration (2.3)
9.2.3.1
Lower calibration point (2.3.1)
Sets distance from sensor reference point to lower calibration point: usually process empty level.
Setting 0 to 120 m
Default 30m
9.2.3.2 Upper calibration point (2.3.2)
Sets distance from sensor reference point to upper calibration point: usually process full level.
Setting 0 to 120 m
Default 0
Parameter assignment
9.2Setup (2)
SITRANS LR500 series with mA/HART
118 Operating Instructions, 03/2024, A5E51099898-AA