Siemens SITRANS LR500 Series - Logging Values Selection; Simulation Parameters; Simulation Mode Selection

Siemens SITRANS LR500 Series
222 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note
Log entr
ies not immediately visible using "Overwrite oldest"
When setting "Overwrite oldest" is used, 30 log entries must be stored internally before any are
visible in the Trend log.
For example, to log Level and Sensor temperature every 10 minutes, it will take 2.5 hours for the
󹪝rst log entries to appear.
Number of logging values = 2
Logging interval = 600
Logging behavior = Overwrite oldest
Logging value 1 = Level
Logging value 2 = Sensor temperature
The Trend log will appear empty until the 󹪝rst 30 entries (15 Level + 15 Sensor temperature) are
stored internally, then written to the log:
A total of 30 log entries required, divided by the Number of logging values (2), stored at a
Logging interval of 600 seconds (10 minutes)
30/2 * 10 = 150 minutes or 2.5 hours
9.3.6.5 Logging value 1(3.6.5)...Logging value8 (3.6.12)
Se
ts value to log.
Setting Level
Space
Distance
Echo signal strength
Con󹪝dence
Volume
Custom
Electronics temperature
Loop current
Default Distance
Echo strength
To edit the logging values, trend logging must be disabled.
9.3.7
Simulation (3.7)
9.3.7.1 Simulation mode (3.7.1)
De󹪝nes whether the simulated value is 󹪝xed or in the shape of a ramp.
Parameter assignment
9.3Maintenance and diagnostics (3)
SITRANS LR500 series with mA/HART
Operating Instructions, 03/2024, A5E51099898-AA 141