WARNING
Loss of explosion protection
Risk of e
xplosion in hazardous areas if the device is open or not properly closed.
• Close the device as described in Installing/mounting (Page35).
WARNING
Opening device in energized state
Risk of e
xplosion in hazardous areas
• Only open the device in a de-energized state.
• Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in
accordance with the directives.
Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in
energized state in hazardous areas.
7.2 General requirements
Bef
ore commissioning, check the following:
• The device is installed and connected in accordance with the guidelines provided in Installing/
mounting (Page35) and Connecting (Page49).
• The device meets the local governing codes and good engineering practises for use in a
critical application, with applicable backup systems and alarms.
7.3 Local operation
The device is built for easy operation, making it possible to be commissioned quickly. Its
parameters are menu-driven and can be modied through local operation, using the display and
buttons, also known as the Human Machine Interface (HMI).
For details on how to use the interface, see Operating (Page85).
Note
U
pdate of process value on display when commissioning wizard run via EDD
Process values shown in measurement view on local display will not automatically update to
reect a change made remotely via "Wizard - Quick start...".
• To have device process values update when congured remotely, use local buttons to take
device in and out of measurement view (i.e. go to parameter view then back
to measurement view).
Commissioning
7.3Local operation
SITRANS LR500 series with mA/HART
62 Operating Instructions, 03/2024, A5E51099898-AA