Button functions for editing
Button Name Function
UP or DOWN
ar
row
Selecting parameter set‐
tings
Scrolls to item
Alpha-numeric editing Increases or decreases value. Pressing and hold‐
ing incr
eases scrolling speed through values.
RIGHT arrow Selecting parameters Accepts the data (writes the parameter setting)
LEFT arrow Selecting parameter set‐
tings
Cancels edit vie
w without changing the param‐
eter setting.
7.6.4 Wizards
7.6.4.1
Wizard overview
Note
Im
portant information regarding the use of commissioning wizard
• Settings for quick start wizard are inter-related and changes apply only after "Finish" is set to
"Yes" in nal step.
• Do not use quick start wizard to modify individual parameters.
Perform customization for your application only after "Quick start" wizard has been
completed.
Note
Par
ameter settings properly stored
To ensure parameter settings are properly stored in the device, wait 30 seconds after any
conguration change before removing power from the device.
Note
No user
-relevant data is lost in the event of a power failure.
1. Press to enter the "Quick start" menu, and again to start the "Quick start" wizard.
2
. Congure each parameter per step, then select "Next" to proceed. In the nal step, when
asked to "Finish", choose "Yes" to save changes.
3. Next, "Exit" the wizard. After exiting the wizard, press
to return to operation view.
In t
he upper left corner of each view, the wizard name appears, followed by each step name.
In the upper right corner, the view number is shown. The number of steps depends on the
actual device variant ordered.
Commissioning
7.6Local commissioning
SITRANS LR500 series with mA/HART